Research Hub

대학 자원

대학 인프라와 자원을 공유해 공동 연구와 기술 활용을 지원합니다.

Loading...

논문 리스트

2009
전류변성기의 포화 검출을 위한 알고리즘 개발 Method for Detection of Saturation of a Current Transformer
대한전기학회
최준호 외 1명
논문정보
Publisher
전기학회논문지B
Issue Date
2009-05-01
Keywords
-
Citation
-
Source
-
Journal Title
-
Volume
58
Number
5
Start Page
879
End Page
884
DOI
ISSN
15982602
Abstract
A method for detection of saturation of a current transformer(CT) is proposed. The algorithm is initiated when the end point of a saturation period is detected. This detection is achieved by checking the time interval between the adjacent zero-crossing points of the second derivative of the secondary current. Once the end point of the saturation period is detected, the beginning point of the corresponding saturation period is determined by backward examination of the sum of the secondary current from the end point. The Electromagnetic Transient Program(EMTP) was used to generate fault current signals for different fault inception angles and different remanent fluxes. The performance evaluation shows that the proposed algorithm successfully detects the saturation period even in the presence of a remanent flux.

저자 정보

이름 소속
최준호 전기공학과