Research Hub

대학 자원

대학 인프라와 자원을 공유해 공동 연구와 기술 활용을 지원합니다.

Loading...

논문 리스트

2022
새로운 DFT 비교기를 이용한 자동 다전원 동기절체 스위치에 관한 연구
한국산업융합학회
박성준, 손경종 외 1명
논문정보
Publisher
한국산업융합학회논문집
Issue Date
2022-06-30
Keywords
-
Citation
-
Source
-
Journal Title
-
Volume
25
Number
3
Start Page
423
End Page
431
DOI
ISSN
1226833x
Abstract
The UPS(Uninterruptible Power Supply) system operates in the battery charging mode when the grid is normal, and in the UPS mode, which is the battery discharge mode when a grid error occurs. Since the UPS must supply the same voltage as the grid to the load within 4 [ms] in case of a grid error, the switching time and power recovery time should be short when controlling the output voltage and current of the UPS, and the power failure detection time is also important. The power outage detection algorithm using DFT(Discrete Fourier Transform) proposed in this paper compares the grid voltage waveform with the voltage waveform including the 9th harmonic generated through DFT using Schmitt trigger to detect power outage faster than the existing power outage monitoring algorithm. There are advantages. Therefore, it is possible to supply instant and stable power when switching modes in the UPS system. The multi-power-applied UPS system proposed in this paper uses DFT, which is faster than the conventional blackout monitoring algorithm in detecting power failure, to provide stable power to the load in a shorter time than the existing power outage monitoring algorithm when a system error occurs. The detection method was applied. The changeover time of mode switching was set to less than ...

저자 정보

이름 소속
박성준 전기공학과
손경종 전기공학과